Revision history [back]
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
2 |
No.2 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
Pump Current
|Pump | Current|
Nameplate kVA
|
Standard Gen Nameplate
kVA submersible
kVA | |------|------|------| |submersible
1
|
150
|
110
375
| 375 |
submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
3 |
No.3 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|Pump | Current| Nameplate kVA | Standard Gen Nameplate kVA
| |------|------|------| |submersible
|
submersible 1 |
-
150
|
- | -
110
|
- | -
375
-
|
submersible 2
| -
100
- | -
110
313
- | - 313 - |
submersible 3
| -
150
- | -
110
375
-| - 375 - |
submersible 4
| -
135
- | -
110
375
- | - 375 - |
horizontal 1
- | -
295
- | -
195
750
- | - 750 - |
horizontal 2
| -
250
- | -
165
750
- | - 750 - |
horizontal 3
| -
295
- | -
195
750
- | - 750 - |
horizontal 4
| -
95
- | -
40
???
- | - ??? - |
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
4 |
No.4 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the
pump motor. This is because when the motor starts there’s a starting surge which could damage or
stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|Pump | Current| Nameplate kVA | Standard Gen Nameplate kVA |
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 -| - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
5 |
No.5 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|Pump | Current| Nameplate kVA | Standard Gen Nameplate kVA |
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 -| - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
Pump | Current | Nameplate kVA | Standard Gen Nameplate kVA |
---|---|---|---|
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 - | - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
6 |
No.6 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
Pump | Current | Nameplate kVA | Standard Gen Nameplate kVA |
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
|Pump | Current| Nameplate kVA | Standard Gen Nameplate kVA |
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 -| - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
Pump | Current | Nameplate kVA | Standard Gen Nameplate kVA |
---|---|---|---|
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 - | - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
7 |
No.7 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|
Current | Nameplate kVA | Standard Gen Nameplate kVA |
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
|Pump
|
Pump |
Current| Nameplate kVA | Standard Gen Nameplate kVA |
submersible 1 | - 150 - | - 110 - | - 375 - |
submersible 2 | - 100 - | - 110 - | - 313 - |
submersible 3 | - 150 - | - 110 -| - 375 - |
submersible 4 | - 135 - | - 110 - | - 375 - |
horizontal 1 - | - 295 - | - 195 - | - 750 - |
horizontal 2 | - 250 - | - 165 - | - 750 - |
horizontal 3 | - 295 - | - 195 - | - 750 - |
horizontal 4 | - 95 - | - 40 - | - ??? - |
Pump | Current |
Pump Current
Nameplate
|
kVA
Standard Gen Nameplate
|
---|---|---|---|
kVA
submersible
|
-
1
150
|
-
110
|
- 375 - |
375
submersible
|
-
2
100
|
-
110
|
- 313 - |
313
submersible
|
-
3
150
|
-
110
|
- 375 - |
375
submersible
|
-
4
135
|
-
110
|
- 375 - |
375
horizontal 1
|
-
295
|
-
195
|
- 750 - |
750
horizontal
|
-
2
250
|
-
165
|
- 750 - |
750
horizontal
|
-
3
295
|
-
195
|
- 750 - |
750
horizontal
|
-
4
95
|
-
40
|
- ??? - |
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
8 |
No.8 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|
Current | Nameplate
|
Standard Gen Nameplate
|
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
9 |
No.9 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
- Pump - | - Current - | - Nameplate kVA - | - Standard Gen Nameplate kVA - |
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
10 |
No.10 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
|
|
|
|
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
11 |
No.11 Revision
|
|
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
Pump - - - - - - - - - - - - | Current - - - - - - - | Nameplate kVA - - - - | Standard Gen Nameplate kVA
|
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert
In general the generator to run a pump should be at least 3 times the nameplate kVA rating of the pump motor. This is because when the motor starts there’s a starting surge which could damage or stall the generator which in turn could damage the pump motor. The corresponding ratings would be
Pump - - - - - - - - - - - - | Current - - - - - - - | Nameplate kVA - - - - | Standard Gen Nameplate kVA |
---|---|---|---|
submersible 1 | 150 | 110 | 375 |
submersible 2 | 100 | 110 | 313 |
submersible 3 | 150 | 110 | 375 |
submersible 4 | 135 | 110 | 375 |
horizontal 1 | 295 | 195 | 750 |
horizontal 2 | 250 | 165 | 750 |
horizontal 3 | 295 | 195 | 750 |
horizontal 4 | 95 | 40 | ??? |
Pump Current Nameplate kVA Standard Gen Nameplate kVA submersible 1 150 110 375 submersible 2 100 110 313 submersible 3 150 110 375 submersible 4 135 110 375 horizontal 1 295 195 750 horizontal 2 250 165 750 horizontal 3 295 195 750 horizontal 4 95 40 ???
(taken from website: https://www.submersibleborepumps.com.au/generator_size_for_pump.html)
From the information provided, it seems the submerisble pumps are running at below capacity (their running current is below their continuous rating). The 40 kVA horizontal pump is running a higher continuous current than its nameplate rating suggests it should. They should review the suitability of this motor or perhaps there’s a typo.
I would not recommend they procure one generator for all of these loads, but break it down into at least 3 or four generators. That’s because they machines will likely not be all connected at the same location, so there will be a voltage drop running from one generator to too many pumps. In addition, it’ll be easier to get smaller generators than one big one. Finally, they should consider a spare if money allows
Michael E. RedR Expert